CATEGORIES

FEATURED PRODUCTS

35KV Outdoor Disconnector Switch GW9-40.5/630A, Pole-mounted, Substation Application

Short Description:
English Summary The GW9-40.5/630A is a single-pole manual disconnector switch designed for 35KV outdoor AC distribution systems, suitable for global medium and high-voltage distribution scenarios (Asia, Africa, Latin America, Middle East, Europe, etc.). It features double-post porcelain/composite silicone rubber insulation, double-blade contacts with self-locking mechanism, enabling circuit switching under voltage but no-load conditions, providing a visible break point for safe maintenance. With anti-pollution, weather-resistant, maintenance-free properties, it operates reliably in -40℃~+40℃ and altitude ≤4000m, widely used for isolation and sectionalization of 35KV substations, pole-mounted transformers, overhead lines, high-voltage distribution in industrial parks, an essential core equipment for 35KV outdoor distribution networks.

一、产品详细描述(Product Description)

 

35KV户外配电系统中,隔离开关是实现电气隔离、线路分段、设备检修的核心设备,必须提供清晰可见断点、可靠绝缘与稳定操作,适配高电压场景下的安全运维需求。传统35KV隔离开关存在污闪风险高、操作笨重、维护量大、地域适配性差等问题,难以适配全球不同气候(高温、高湿、盐雾、重污秽、高原)与地域环境。

GW9-40.5/630A户外高压隔离开关针对性解决以上痛点,专为35KV高压场景量身打造:

  1. 核心功能:仅在有电压无负载条件下分合电路,可分合≤2A的空载容性/感性电流,严禁带负荷操作;合闸后自动自锁,防止误分误合,有效保障运维人员人身安全与设备稳定运行。
  2. 结构优势:单极双柱结构,双刀片触头+压缩弹簧确保接触压力≥150N、接触电阻≤120μΩ,导电稳定、损耗低;支柱绝缘子可选瓷质(防污型)/复合硅橡胶,爬电距离充足(适配35KV高压绝缘需求),抗污闪、耐盐雾、抗紫外线,杜绝高压场景下的绝缘隐患。
  3. 操作便捷手动绝缘钩棒操作,力矩适中、动作灵活,无需外接电源,适配全球无电/偏远地区的35KV配网场景;安装方式灵活,柱上垂直/水平安装,接线简单,可快速完成安装调试。
  4. 环境适配:工作温度-40℃~+40℃,海拔≤4000m,抗震≤8级,适配沿海盐雾、工业污秽、高原缺氧、热带/寒带极端气候等全球多地域场景;热镀锌底座+不锈钢固件,耐腐蚀、抗老化、免维护,大幅降低运维成本。
  5. 应用场景:广泛用于35KV户外配网,包括35KV变电站母线隔离、柱上变压器前端保护、架空线路分段、工业园区高压配电、农村电网升级、新能源电站配套,符合GB 1985、IEC 62271-102标准,各项性能指标均满足全球中高压配网的使用要求。

Description

In 35KV outdoor distribution systems, disconnector switches are core equipment for electrical isolation, line sectionalization, and equipment maintenance, requiring clear visible break points, reliable insulation, and stable operation to meet the safe operation and maintenance needs of high-voltage scenarios. Conventional 35KV disconnectors face issues such as high pollution flashover risk, cumbersome operation, high maintenance, and poor regional adaptability, making them difficult to adapt to global diverse climates (high temperature, high humidity, salt spray, heavy pollution, plateau) and regional environments.

GW9-40.5/630A Outdoor High Voltage Disconnector Switch specifically addresses the above pain points and is tailored for 35KV high-voltage scenarios:

  1. Core Function: Switches circuits only under voltage but no-loadconditions, capable of switching no-load capacitive/inductive currents ≤2A; strictly prohibited from load operation. It self-locks automatically after closing to prevent accidental opening and closing, effectively ensuring the personal safety of operation and maintenance personnel and the stable operation of equipment.
  2. Structural Advantages: Single-pole double-post structure, double-blade contacts with compression springsensure contact pressure ≥150N and contact resistance ≤120μΩ, with stable conduction and low loss. Post insulators are available in porcelain (anti-pollution)/composite silicone rubber, with sufficient creepage distance (adapting to 35KV high-voltage insulation requirements), anti-pollution flashover, salt spray resistance, and UV resistance, eliminating insulation hazards in high-voltage scenarios.
  3. Easy Operation: Manual operation with insulated hook stick, moderate torque, flexible action, no external power supply required, suitable for 35KV distribution scenarios in off-grid/remote areas around the world. Flexible installation: pole-mounted vertical/horizontal, simple wiring, and quick installation and commissioning.
  4. Environmental Adaptability : Operating temperature -40℃~+40℃, altitude ≤4000m, seismic resistance ≤8 degrees, suitable for coastal salt spray, industrial pollution, high-altitude hypoxia, tropical/cold extreme climatesand other global regional scenarios. Hot-dip galvanized base + stainless steel fasteners, corrosion-resistant, anti-aging, maintenance-free, greatly reducing operation and maintenance costs.
  5. Application Scenarios: Widely used in 35KV outdoor distribution networks, including 35KV substation busbar isolation, pole-mounted transformer front-end protection, overhead line sectionalization, high-voltage distribution in industrial parks, rural power grid upgrading, new energy power station supporting, compliant with GB 1985, IEC 62271-102standards, and all performance indicators meet the usage requirements of global medium and high-voltage distribution networks.

 

二、产品参数表(Parameters Table)

中文参数项 参数值 English Parameter Value
产品型号 GW9-40.5/630A Product Model GW9-40.5/630A
额定电压 40.5kV(适配35KV) Rated Voltage 40.5kV (suitable for 35KV)
额定电流 630A Rated Current 630A
额定频率 50Hz/60Hz Rated Frequency 50Hz/60Hz
1min工频耐受电压(对地) 95kV(有效值) 1min Power Frequency Withstand Voltage (Phase to Ground) 95kV (RMS)
雷电冲击耐受电压(对地) 200kV(峰值) Lightning Impulse Withstand Voltage (Phase to Ground) 200kV (Peak)
额定短时耐受电流 31.5kA/4s Rated Short-time Withstand Current 31.5kA/4s
额定峰值耐受电流 80kA Rated Peak Withstand Current 80kA
接触电阻 ≤120μΩ Contact Resistance ≤120μΩ
机械寿命 ≥10000次 Mechanical Life ≥10000 Operations
绝缘材质 瓷质/复合硅橡胶(防污型) Insulation Material Porcelain/Composite Silicone Rubber (Anti-pollution)
操作方式 手动(绝缘钩棒) Operation Mode Manual (Insulated Hook Stick)
安装方式 户外柱上(垂直/水平) Installation Outdoor Pole-mounted (Vertical/Horizontal)
环境温度 -40℃~+40℃ Ambient Temp -40℃~+40℃
适用海拔 ≤4000m Applicable Altitude ≤4000m
执行标准 GB 1985、IEC 62271-102 Compliance GB 1985, IEC 62271-102